Notă:
Due to dangerous overvoltage and overheating, the Current Transformator is not allowed to be operated with open secondary Side. (EN 60044-1 /A2) As soon as the Measurement Device, the Energy Counter or the Net Analyzer is disconnected, the secondary Side has to be shortcutted!
Metodă de montaj:
Prin pini
Rated dynamic current Idyn:
2.5Ith
Max. Operating voltage Um:
0.72kV r.m.s.
Short-time current Ith:
< 60Ipr
Reference temperature:
23°C ±1°C
Bare colectoare maxim:
30x10
Thermal rated continuous current according to EN60044-1:
##
Cablu de conexiune:
lengh 100cm;Cross-section 14AWG / 2.08mm²
Gama de temperatură - Funcţionare:
-15 to +50
Rated current secondary side Isr:
5A
Housing material:
Polycarbonate, self-extinguishing
Winding primary side:
Cable and busbar feedthrough
Temperatura maximă a mediului ambiant:
75
Isolation:
Class B (EN60044-1);Class E (EN60044-1)
Accesorii opționale:
MGF39000--;MGF37900--;MGX20006--;MGX20406--
Gama de temperatură - Transport/Depozitare:
-25 to +75
Rated current primary side Ipr:
250
Insulation requirements:
##
Load current error:
For class 0.5 and 5% In: ±1.5%;For class 0.5 and 20% In: ±0.75%;For class 0.5 and 100% In: ±0.5%;For class 0.5 and 120% In: ±0.5%;For class 0,5 and 150% In: ±0,5%
Temperatura minimă a mediului ambiant:
-25
Categorie produs:
Normal installation (DIN EN 61869-2)
Standard produs:
EN 61869-2
Isolation test voltage :
3 kV R.M.S. 50 Hz/1min
Intended use:
for copper bars up to 30 x 15mm
Diametru maxim conductor:
36
Versiune:
Dry type transformer, air insulation